Skip to main content
Applications
Applications · LRI AEM-60DC8

Solar string and DC UPS monitoring

Voltage supervision of PV strings and DC UPS with AEM-60DC8: per-string voltage, bus voltage and temperature. Modbus RTU and SCADA integration.

LRI Engineering2026-05-269 min

The problem

Photovoltaic plants — from 75 kW distributed generation to multi-MW utility-scale — suffer from invisible losses on individual strings. A module with a microcrack, an oxidized MC4 connector or accumulated dirt degrades string power without triggering any inverter alarm, which continues reporting "OK" while the customer loses generation. In DC UPS for critical missions (data center, hospital, sensitive industrial process), silent failure of a battery string between scheduled tests is the dangerous equivalent. In both cases, the operator needs continuous per-string visibility, with granularity that makes mismatch detectable in hours — not in quarterly O&M cycles — and without violating the isolation voltage of the DC bus.

Golden rule: the inverter reports the aggregate; the problem lives in the string.

Typical topology

Small and medium PV plants typically have 4 to 12 strings in parallel connected to a combiner box, then to the inverter. String voltage in standard conditions (STC) ranges from 400 to 1000 VDC depending on the design. DC UPS have battery strings (lead-acid or LiFePO4) in parallel forming a 220 to 480 VDC bus.

PV strings (8x example)
   |    |    |    |    |    |    |    |
   v    v    v    v    v    v    v    v
+---+--+---+--+---+--+---+--+---+--+---+
|       voltage of each string (V)    |
+---+--+---+--+---+--+---+--+---+--+--+
   |    |    |    |    |    |    |    |
   +----+----+----+----+----+----+----+
        |
        v
   DC combiner + disconnect switch
        |
        v
+----------------+
| PV inverter or |
| DC UPS         |
+----------------+

Sensing:
+--------------+
| AEM-60DC8 x N| <-- 100:1 divider for string voltage
+--------------+
       |
       v
   Modbus RTU --> Gateway --> SCADA / generation portal

For string voltages above 200 VDC, all voltage channels use a precision resistive divider with class ≤0.5%. The AEM-60DC8 input is non-isolated with common GND: interface and safety design must be validated with engineering.

Golden rule: one voltage channel per string is what locates which string left its expected point.

What to measure and why

In PV plants and DC UPS, these quantities are priorities. The AEM-60DC8 measures DC voltages (8 channels) and temperature through a single NTC; current and irradiance are outside the scope of the device:

Quantity Justification
Per-string voltage (V) Confirms operation at maximum power point; STC drop indicates open-circuit module.
DC bus voltage (V) Combiner output; inverter or UPS input.
Ambient temperature (deg C) Reference for interpreting string voltage, which varies with temperature. Read through a single 10K NTC (±1 deg C).

For DC UPS, per-battery-string voltage remains applicable; charge/discharge current is outside the scope of the AEM-60DC8.

Golden rule: string voltage without a temperature reference triggers false alarms on weather swings.

Sizing — how many AEM-60DC8?

Formula:

N_AEM = ceil( (N_strings + bus_channels) / 8 )

Where each string takes 1 voltage channel.

Simplified example for PV plant with 6 strings at 500 VDC:

  • 6 strings × 1 channel = 6 channels (via external divider or transducer)
  • Bus: 1 voltage = 1 channel
  • Temperature: 1 dedicated NTC (does not use a channel)
  • Total: 7 channels → 1 AEM-60DC8 (with 1 free channel for expansion)

Simplified example for 380 VDC DC UPS with 4 battery strings:

  • 4 strings × 1 channel = 4 channels
  • Bus: 1 voltage = 1 channel
  • Temperature: 1 dedicated NTC (does not use a channel)
  • Total: 5 channels → 1 AEM-60DC8

Golden rule: size counting future inverters and UPS — expansion without spare hardware requires reinstall.

Recommended setpoints and alarms

Variable Warning Critical Automatic action
PV string voltage STC normalized (%) <90 <80 Module degradation alert
DC UPS bus voltage (V) ±5% nominal ±10% nominal Flag UPS off-spec
Battery string temperature (deg C) >35 >45 Reduce float current

Limits are written to holding registers protected by firmware v1.03 Secure by Design.

Golden rule: alarms relative to the string average (not absolute) eliminate noise in string voltage.

SCADA / PLC integration

The AEM-60DC8 operates as a Modbus RTU Slave. Recommended baudrate 19200 bps for small plants and 57600 bps for plants with 6+ AEM-60DC8 on the same bus.

Ignition: use the Solar module to create UDTs per string with voltage and alarm attributes. History in Tag Historian with 5-year retention for seasonal analysis.

Elipse E3: the IODriver-Modbus driver integrates the AEM-60DC8 units and the pyranometer on the same gateway. ECMA script-calculated tags produce PR and mismatch detection.

AVEVA Insight (or System Platform): for distributed plants, the cloud connector pushes data from each plant for comparative analysis between sites — a relevant differentiator in portfolios with 20+ plants.

For SaaS generation portals (PVcase, Solar-Log, Meteocontrol), the gateway converts Modbus RTU to Modbus TCP or MQTT. Keep the AEM-60DC8 behind an industrial firewall.

See whitepaper WP01 for Modbus RTU over Secure by Design details.

Golden rule: SaaS generation portal is integration, not a substitute for local SCADA — design for both.

Regulatory compliance

PV and DC UPS systems follow specific standards:

  • ABNT NBR 16690 (electrical installations for PV arrays)
  • ABNT NBR 16149 (grid-connected PV systems — requirements)
  • IEC 62548 (Photovoltaic arrays — design requirements), including isolation monitoring requirements
  • IEC 61724-1 (Photovoltaic system performance monitoring)
  • IEC 62040-1 and IEC 62040-3 (UPS — safety and performance) for DC UPS
  • IEEE 1547-2018 (interconnection of distributed energy resources)
  • IEC 62443-4-2 — AEM-60DC8 aligned, without formal certification, for the cybersecurity layer
  • ANEEL REN 1,000/2021 and updates of distributed generation in Brazil

The AEM-60DC8 forensic telemetry contributes to the performance report required in IEC 61724-1 Class A.

Golden rule: PV standards evolve quickly — check the current ABNT and IEC editions before closing a project.

Illustrative case

Illustrative example, without field data: in a plant with several strings in parallel, reading each string voltage on an AEM-60DC8 channel (through an external divider or isolated transducer) reveals an open-circuit or disconnected string that the aggregate inverter reading can mask. Degradations that change current without changing voltage in a resolvable way (±1% FS) require external current measurement and are not detected by the device.

Golden rule: per-string measurement is the difference between auditing the plant and guessing where the problem is.

Deployment checklist

  1. Survey topology (number of strings, STC voltage, combiner configuration).
  2. Specify 100:1 class ≤0.5% resistive dividers for strings >200 VDC.
  3. Define, with engineering, the voltage interface for each string (external divider or isolated transducer).
  4. If irradiance or current measurement is needed, use external instrumentation connected to the SCADA, not to the AEM-60DC8.
  5. Compute N_AEM and provide 2 reserve channels per unit.
  6. Place AEM-60DC8 inside the combiner box or dedicated cubicle.
  7. 24 AWG shielded twisted-pair cable, shield grounded at a single point.
  8. Configure baudrate 57600 bps in plants with 6+ units.
  9. Validate 147 holding registers and enable forensic telemetry.
  10. Document baseline on a clear day, near the solstice, as reference.

Golden rule: baseline on a clear day near the solstice is the only valid reference for the whole year.

FAQ

See the FAQ block in the frontmatter of this page.

Related content

More LRI technical materials on adjacent topics.