LRI-AEM-60DC8 · v1.03

Mapa Modbus RTU

Mapa completo de holding registers do LRI-AEM-60DC8 para integradores de SCADA e CLP.

Protocolo

Transporte

RTU over RS-485 half-duplex

Framing

8N1 (8 data bits, no parity, 1 stop bit)

Function codes

  • 03·Read Holding Registers
  • 16·Write Multiple Registers

Exceções

  • 02·Illegal data address

Holding registers

EndereçoNomeTipoEscalaUnidadeAcessoDescrição
Medição
40001Voltage 1uint16×100VRInput voltage channel 1 (ADC reading)
40002Voltage 2uint16×100VRInput voltage channel 2 (ADC reading)
40003Voltage 3uint16×100VRInput voltage channel 3 (ADC reading)
40004Voltage 4uint16×100VRInput voltage channel 4 (ADC reading)
40005Voltage 5uint16×100VRInput voltage channel 5 (ADC reading)
40006Voltage 6uint16×100VRInput voltage channel 6 (ADC reading)
40007Voltage 7uint16×100VRInput voltage channel 7 (ADC reading)
40008Voltage 8uint16×100VRInput voltage channel 8 (ADC reading)
40009NTC Temperatureint16×100°CRMeasured NTC 10K temperature
Thresholds
40010NTC Min Thresholdint16×100°CR/WMinimum temperature alarm limit
40011NTC Max Thresholdint16×100°CR/WMaximum temperature alarm limit
40012CH1 Min Thresholduint16×100VR/WChannel 1 minimum voltage alarm limit
40013CH1 Max Thresholduint16×100VR/WChannel 1 maximum voltage alarm limit
40014CH2 Min Thresholduint16×100VR/WChannel 2 minimum voltage alarm limit
40015CH2 Max Thresholduint16×100VR/WChannel 2 maximum voltage alarm limit
40016CH3 Min Thresholduint16×100VR/WChannel 3 minimum voltage alarm limit
40017CH3 Max Thresholduint16×100VR/WChannel 3 maximum voltage alarm limit
40018CH4 Min Thresholduint16×100VR/WChannel 4 minimum voltage alarm limit
40019CH4 Max Thresholduint16×100VR/WChannel 4 maximum voltage alarm limit
40020CH5 Min Thresholduint16×100VR/WChannel 5 minimum voltage alarm limit
40021CH5 Max Thresholduint16×100VR/WChannel 5 maximum voltage alarm limit
40022CH6 Min Thresholduint16×100VR/WChannel 6 minimum voltage alarm limit
40023CH6 Max Thresholduint16×100VR/WChannel 6 maximum voltage alarm limit
40024CH7 Min Thresholduint16×100VR/WChannel 7 minimum voltage alarm limit
40025CH7 Max Thresholduint16×100VR/WChannel 7 maximum voltage alarm limit
40026CH8 Min Thresholduint16×100VR/WChannel 8 minimum voltage alarm limit
40027CH8 Max Thresholduint16×100VR/WChannel 8 maximum voltage alarm limit
Configuração
40028Baudrate Indexuint16R/WCommunication baudrate selector (see baudrate table)
40029Slave IDuint16RModbus slave address (set via DIP switch)

Tabela de baudrate (40028)

A baudrate é selecionada por índice — escreva o índice em 40028, não o valor numérico.

ÍndiceBaudrate
04,800 bps
19,600 bps
219,200 bps
338,400 bps
457,600 bps
5115,200 bps